Engineering ToolBox > Adding Kv or Cv values

Adding Kv or Cv when control valves are in series or parallel

Control Valves in Parallel

control valves in parallel

The resulting Kv or Cv if two valves are installed in parallel can be calculated as

Kvt = Kv1 + Kv2  (1)

where

Kvt = resulting Kv

Kv1 = Kv valve 1

Kv2 = Kv valve 2

Control Valves in Series

control valves series

The resulting Kv or Cv if two valves are installed in series can be calculated as

1 / (Kvt)2 =  1 / (Kv1)2 + 1 / (Kv2)2   (2)