Engineering ToolBox > Air Ducts Minor Loss Coefficient Diagrams

Minor loss coefficient diagrams for air ductwork, bends, expansions, inlets and outlets  - SI units

Minor loss in air ducts based on a summarized minor loss coefficient and air flow velocity can be estimated with the diagram below:

minor loss diagram air ductwork

Minor loss for some common ductwork components like bends, expansions, inlets and outlets can be estimated with the diagrams below.

Minor Loss Coefficients - Bends

The minor loss coefficients in 90o bends can be estimated with the diagram below.

air ducts minor loss resistance coefficient in bends

The minor loss in bends 0 - 180o can be estimated with the equation

ξ0-180 = ξ90 α / 90   (1)

where

ξ0-180 = minor loss coefficient for the bend with the actual angle

ξ90 = minor loss coefficient for the 90o bend according the diagram above

α = angle of the actual bend

The minor loss coefficient in a 90o bend like the one below is 1.0.

air ducts minor loss resistance coefficient in 90 bend

Minor Loss Coefficients - Expansions

minor loss coefficients diagram - expansions

Minor Loss Coefficients - Inlets

minor loss air ducts inlets

Minor Loss Coefficients - Outlets

minor loss air ducts outlets