ASME B31.9 Building Services Piping applies to the following building services:
The working pressure and temperature limits of B31.9 can be summarized to:
| Service | Temperature Limits | Pressure Limit |
| Steam and condensate | maximum 366oF (186oC), minimum 0oF (-18oC) | 150 psig (1000 kPa) |
| Air, gases and vapors | maximum 200oF (93oC), minimum 0oF (-18oC) | 150 psig (1000 kPa) |
| Nonflammable Liquids | maximum 250oF (121oC), minimum 0oF (-18oC) | 350 psig (2300 kPa) |