Engineering ToolBox > Sizing Circular Ducts
Maximum air velocity in the ducts should be kept below certain limits to avoid unacceptable generation of noise.

The values from the table below can be used to rough sizing of ducts in comfort, industrial and high speed ventilation systems.
| Maximum Air Volume Flow (m3/h) | ||||||||||
| Diameter (mm) | Area (m2) | Comfort systems | Industrial systems | High speed systems | ||||||
| Main ducts | Secondary ducts | Connecting ducts | Main ducts | Secondary ducts | Connecting ducts | Main ducts | Secondary ducts | Connecting ducts | ||
| Speed (m/s) | ||||||||||
| 5.5 | 4 | 2 | 10 | 6.5 | 4 | 14 | 9 | 6.5 | ||
| 63 | 0.003 | 62 | 45 | 22 | 112 | 73 | 45 | 157 | 101 | 73 |
| 80 | 0.005 | 99 | 72 | 36 | 181 | 118 | 72 | 253 | 163 | 118 |
| 100 | 0.008 | 155 | 113 | 57 | 283 | 184 | 113 | 396 | 254 | 184 |
| 125 | 0.012 | 243 | 177 | 88 | 442 | 287 | 177 | 618 | 397 | 287 |
| 160 | 0.020 | 398 | 289 | 145 | 723 | 470 | 289 | 1013 | 651 | 470 |
| 200 | 0.031 | 622 | 452 | 226 | 1130 | 735 | 452 | 1583 | 1017 | 735 |
| 250 | 0.049 | 971 | 707 | 353 | 1766 | 1148 | 707 | 2473 | 1590 | 1148 |
| 315 | 0.078 | 1542 | 1122 | 561 | 2804 | 1823 | 1122 | 3926 | 2524 | 1823 |
| 400 | 0.126 | 2487 | 1809 | 904 | 4522 | 2939 | 1809 | 6330 | 4069 | 2939 |
| 500 | 0.196 | 3886 | 2826 | 1413 | 7065 | 4592 | 2826 | 9891 | 6359 | 4592 |
| 630 | 0.312 | 6169 | 4487 | 2243 | 11216 | 7291 | 4487 | 15703 | 10095 | 7291 |
| 800 | 0.502 | 9948 | 7235 | 3617 | 18086 | 11756 | 7235 | 25321 | 16278 | 11756 |
| 1000 | 0.785 | 15543 | 11304 | 5652 | 28260 | 18369 | 11304 | 39564 | 25434 | 18369 |
| 1250 | 1.227 | 24286 | 17663 | 8831 | 44156 | 28702 | 17663 | 61819 | 39741 | 28702 |