Resources, Tools and Basic Information for Engineering and Design of Technical Applications!

Resources, Tools and Basic Information for Engineering and Design of Technical Applications!

mobile - visible on handheld devices - alternatively go to www.engineeringtoolbox.com!

Engineering ToolBox > Classification of Gas Oil

Classification of gas oil based on BS 2869 - Specification for fuel oils for agricultural, domestic and industrial engines and boilers

Classification of gas oil based on BS (British Standard) 2869 - Specification for fuel oils for agricultural, domestic and industrial engines and boilers

Fuel Class to BS 2869 Kinematic viscosity Flash point. closed Sulphur content per cent by mass Minimum temperature for storage
oC
Minimum temperature for outflow from storage and handling
oC
Application
cSt at 40oC cSt at 100oC Abel min.oC Pensky-Martin min oC
Kerosene C1 43 0.04 ambient ambient Distillate fuel for free standing flueless domestic appliances
Gas oil C2 1.0 - 2.0 38 0.2 ambient ambient Similar vaporizing and atomizing burners on domestic appliances with flues
D 1.5 - 5.5 56 0.5 ambient ambient Distillate fuel for atomizing burners for domestic and industrial use
Heavy fuel oil E 8.2 max 66 3.5 10 10 Residual or blended fuels for atomizing burners normally requiring preheating before combustion in burner
F 20 max 66 3.5 25 30
G 40 max 66 3.5 40 50