Engineering ToolBox > Generation of Condensate in Cold Steam Pipes - SI Units
The diagram and table below can be used as a roughly estimate of the warm-up condensate load generated when the steam system is heated up.

| Condensate Load (kg/100 m) | ||||||||||||||
| Steam Pressure (bar) | Nominal Pipe Dimension (mm) | |||||||||||||
| 50 | 65 | 80 | 100 | 125 | 150 | 200 | 250 | 300 | 350 | 400 | 450 | 500 | 600 | |
| 0 | 9.2 | 14.4 | 19 | 27 | 37 | 47 | 71 | 101 | 134 | 159 | 208 | 262 | 308 | 309 |
| 0.35 | 10 | 15.9 | 20.8 | 29 | 40 | 52 | 69 | 112 | 146 | 174 | 227 | 287 | 338 | 470 |
| 0.7 | 11.3 | 17.8 | 23.4 | 33 | 45 | 58 | 88 | 125 | 165 | 196 | 255 | 322 | 379 | 529 |
| 1 | 12.2 | 19.5 | 25.4 | 36 | 50 | 64 | 96 | 135 | 179 | 212 | 277 | 350 | 412 | 575 |
| 2.5 | 13.4 | 21.3 | 27.8 | 39 | 53 | 70 | 105 | 148 | 195 | 232 | 303 | 383 | 450 | 627 |
| 4 | 15.8 | 25.2 | 33 | 47 | 63 | 82 | 123 | 175 | 233 | 276 | 360 | 454 | 535 | 745 |
| 5.5 | 17.8 | 28 | 37 | 52 | 71 | 92 | 138 | 196 | 260 | 308 | 402 | 507 | 598 | 832 |
| 7 | 19.3 | 30.6 | 40 | 57 | 77 | 100 | 151 | 214 | 284 | 335 | 438 | 553 | 651 | 906 |
| 8.5 | 20.1 | 31.8 | 42 | 59 | 80 | 104 | 157 | 223 | 293 | 349 | 455 | 574 | 676 | 942 |
| 10 | 20.8 | 33.1 | 43 | 62 | 83 | 108 | 162 | 230 | 305 | 361 | 472 | 595 | 700 | 997 |
| 12 | 22.6 | 35.8 | 47 | 67 | 90 | 117 | 176 | 250 | 331 | 392 | 513 | 646 | 760 | 1059 |
| 14 | 24.2 | 38.2 | 50 | 71 | 96 | 125 | 189 | 267 | 353 | 418 | 546 | 689 | 811 | 1130 |
| 16 | 28.1 | 45 | 58 | 83 | 113 | 146 | 219 | 312 | 412 | 489 | 638 | 805 | 947 | 1320 |
| 20 | 36 | 55 | 74 | 108 | 150 | 205 | 312 | 463 | 637 | 764 | 981 | 1228 | 1503 | 1700 |
| 25 | 39 | 59 | 80 | 117 | 162 | 222 | 338 | 502 | 692 | 828 | 1065 | 1362 | 1631 | 2315 |
| 30 | 41.5 | 64 | 85 | 124 | 173 | 237 | 360 | 534 | 735 | 882 | 1134 | 1420 | 1763 | 2464 |
| 40 | 44.3 | 68 | 91 | 132 | 184 | 253 | 385 | 570 | 784 | 940 | 1210 | 1514 | 1852 | 2627 |