Engineering ToolBox > Capacities of Condensate Lines - in kW

Maximum capacities of condensate lines in kW steam consumption

The table below can be used to determine the sizes of a condensate pipe line where the heat consumption in kW is known.

Steam Consumption (kW)
Nominal pipe size Wet main Dry main with gradient Vented Pipes
in mm 1 in 200 ft 1 in 600 ft Vertical
1/2 15 30 10 6 10 12
3/4 20 70 30 18 30 47
1 25 120 50 34 50 94
1 1/4 32 300 120 80 120 211
1 1/2 40 420 176 117 176 293
2 50 760 350 225 350 530
2 1/2 65 1900 800 510 800 1200
3 80 2700 1200 740 1200 1870