Engineering ToolBox > Directivity Coefficient and Sound Attenuation
For a continuing sound source, the sound level in a room is the sum of direct and reverberant sound. The sound pressure for a receiver can be expressed as:
Lp = Lw + log( D / ( 4 Π r2 ) + 4 / R) (1)
where
Lp = received sound pressure level (dB)
Lw = sound power level from source (dB)
D = directivity coefficient
R = room constant (m2 sabin)
Π = 3.14
r = distance from source (m)
The figure below can be used to approximate the Directivity coefficient - D - for typical locations of the receiver and the sound source:

(1) can be transformed to express the difference between the received sound pressure and emitted sound power - the attenuation - as:
Lp - Lw = 10 log( D / ( 4 Π r2 ) + 4 / R) (2)
Combining (2) with the ratio between distance - r - from source and square of the directivity coefficient - D, and the rooms absorption - m2 Sabine, the attenuation - Lp - Lw - can be estimated from the diagram below: