Engineering ToolBox > Drainage Fixture Unit Loads for Sanitary Piping

Maximum Drainage Fixture Unit Loads for sanitary piping

The maximum permissible Drainage Fixture Unit (DFU) loads for sanitary piping can be estimated with the table below.

Maximum Drainage Fixture Units - Stacks and Horizontal Fixture Branches

Maximum Drainage Fixture Units (DFU)
Pipe Size Horizontal fixture branch Stacks less than 3 stories in height Stacks more than 3 stories high
NPS
(inches)
DN
(mm)
Total for stack Total for one story
1 1/20) 40 3 4 8 2
20) 50 6 10 24 6
2 1/20) 65 12 20 42 9
3 80 201) 481) 722) 201)
4 100 160 240 500 90
5 125 360 540 1100 200
6 150 620 960 1900 350

0) No water closet permitted

1) Maximum two water closets

2) Maximum six water closets

Maximum Drainage Fixture Units - Building Drains and Building Drain Branches from Stacks

Maximum Drainage Fixture Units (DFU)
Pipe Size Slope in/ft (cm/m)
NPS
(inches)
DN
(mm)
1/4 (2.1) 1/2 (4.2)
20) 50 21 26
2 1/20) 65 24 31
3 80 421) 501)
4 100 216 250
5 125 480 575
6 150 840 1000