Engineering ToolBox > Fuels - Combustion Air and Flue Gas

Combustion air and flue gas for common fuels as coke, oil, wood, natural gas and more

Combustion air and flue gas for some common fuel gases, solids and fluids can be found in the table below:

Fuel Theoretical air for combustion
Volume at standard pressure
Theoretical flue gas
Volume at standard pressure
Solids (m3/kg) (ft3/lb) (m3/kg) (ft3/lb)
Anthracite 9.4 150 9.5 152
Bituminous coal 6.9 110 7 112
Charcoal 8.4 134 8.4 135
Coke 8.4 134 8 135
Lignite 5.7 92 8.4 93
Peat 5.7 92 5.9 94
Semi anthracite 8.4 135 8.6 137
Wood (dry) 4.4 70 5 80
Gas (m3air/m3fuel) (ft3air/ft3fuel) (m3air/m3fuel) (ft3air/ft3fuel)
Butane C4H10 31 31 27 27
Natural gas 9.5 9.5 8.5 8.5
Propane C3H8 24 24 22 22
Town gas 4 4 3.8 3.8
Fluids (m3air/literfuel) (ft3air/galfuel) (m3air/literfuel) (ft3air/galfuel)
Gas oil

9.8

1570 10.4 1670
Heavy fuel oil 10.8 1730 11.6 1860