The total heat can be expressed as:
h = cp ρ q dt
= 1 (Btu/lbm oF) 8.33 (lbm/gal) q (gal/min) 60 (min/h) dt (oF)
= 500 q dt (1)
where
h = heat load (Btu/h)
cp = 1 (Btu/lbm oF) for water
ρ = 8.33 (lbm/gal) for water
q = water volume flow rate (gal/min)
dt = temperature difference (oF)
Evaporator water flow rate can be expressed as
qevap = 24 hevap / dt (2)
where
qevap = evaporator water flow rate (gallons per minute - gpm)
hevap = air condition load (tons = 15,000 Btu/h = 3,782 k Calories/h)
Condenser water flow rate can be expressed as
qcond = 30 hcond / dt (2)
where
qcond = condenser water flow rate (gallons per minute - gpm)
hcond = air condition load (tons = 15,000 Btu/h = 3,782 k Calories/h)