Engineering ToolBox > Yearly Heat Loss from Steam Pipes
The yearly loss is estimated for pipes with a steam pressure of 6.5 bar and surrounding air temperature of 20oC. Increasing the steam pressure will increase the temperature and influence on the energy consumption and heat loss.
| Pipe dimension (mm) | Heat Loss (W) | Production time (hours) | Fuel Consumption | |||
| Coal (kg) | Oil (kg) | |||||
| Uninsulated | Insulated | Uninsulated | Insulated | |||
| 25 | 313 | 2000 | 119 | 30 | 59 | 15 |
| 6000 | 357 | 89 | 178 | 45 | ||
| 8400 | 505 | 126 | 253 | 64 | ||
| 32 | 430 | 2000 | 166 | 42 | 82 | 21 |
| 6000 | 500 | 125 | 265 | 62 | ||
| 8400 | 699 | 174 | 349 | 88 | ||
| 50 | 529 | 2000 | 202 | 50 | 101 | 25 |
| 6000 | 607 | 152 | 303 | 76 | ||
| 8400 | 755 | 189 | 378 | 92 | ||
| 80 | 748 | 2000 | 297 | 74 | 149 | 37 |
| 6000 | 892 | 223 | 446 | 111 | ||
| 8400 | 1249 | 312 | 625 | 156 | ||
| 100 | 940 | 2000 | 327 | 82 | 164 | 42 |
| 6000 | 981 | 245 | 491 | 131 | ||
| 8400 | 1517 | 379 | 758 | 190 | ||