Engineering ToolBox > Heat Loss from Steam Pipes (btu/h per ft)
The heat loss is a function of the pipe size and insulation quality, the steam temperature (pressure) and the surrounding temperature.
The table below can be used for estimating heat loss from uninsulated steam pipes:
| Heat Loss (btu/h per ft) | ||||||||||
| Temperature Difference between Steam and Surrounding Air (oF) | Dimension (inches) | |||||||||
| 1/2 | 3/4 | 1 | 1 1/4 | 1 1/2 | 2 | 2 1/2 | 3 | 4 | 6 | |
| 100 | 56 | 68 | 82 | 107 | 113 | 138 | 163 | 194 | 243 | 337 |
| 120 | 71 | 85 | 104 | 127 | 142 | 175 | 206 | 246 | 308 | 427 |
| 140 | 86 | 104 | 127 | 155 | 173 | 212 | 251 | 300 | 375 | 521 |
| 160 | 103 | 125 | 152 | 186 | 213 | 256 | 301 | 360 | 451 | 626 |
| 180 | 121 | 146 | 176 | 217 | 243 | 297 | 351 | 417 | 522 | 725 |
| 200 | 139 | 171 | 206 | 251 | 282 | 346 | 408 | 488 | 622 | 850 |
| 225 | 166 | 199 | 243 | 297 | 334 | 410 | 483 | 578 | 726 | 1009 |
| 250 | 192 | 233 | 284 | 347 | 389 | 478 | 563 | 674 | 849 | 1180 |
| 275 | 220 | 266 | 326 | 398 | 447 | 550 | 649 | 778 | 978 | 1360 |
| 300 | 251 | 304 | 372 | 455 | 510 | 628 | 742 | 888 | 1140 | 1557 |
| 325 | 285 | 343 | 425 | 520 | 580 | 705 | 843 | 1010 | 1240 | 1730 |
| 350 | 322 | 388 | 480 | 590 | 660 | 790 | 945 | 1130 | 1358 | 1930 |