An adult at rest breathes 16 respiration per minute - approximately 5 m3/h (lungs volume 4 - 6 liter). With harder work the rate is 3 to 6 times more (15 - 30 m3/h).
The average composition of exhaled air is
- Oxygen 16.5%
- Carbon dioxide 4.0%
- Nitrogen and Argon 79.5%
The quantity of carbon dioxide exhaled in 24 hrs is about 1 kg.
Heat is generated within the human body by the combustion of food. The heat is lost from the body by
- Conduction and convection - about 25%
- Radiation - about 43%
- Evaporation and moisture - about 30%
- Exhaled air - about 2%
Evaporation prevails at high ambient temperatures. Conduction and convection prevails at low ambient temperatures. Heat is liberated in a rate maintaining the internal body temperature at 37oC.
The total heat loss from an adult at normal activity is approximately 118 W (2 Met) in at room with temperatures between 19oC and 34oC.
| Dry bulb temperature oC | 10 | 14 | 18 | 22 | 26 | 30 | 34 |
| Sensible heat (W) | 135 | 112 | 100 | 95 | 84 | 59 | 29 |
| Latent heat (W) | 22 | 22 | 22 | 24 | 34 | 59 | 90 |
| Total heat (W) | 157 | 134 | 122 | 118 | 118 | 118 | 119 |