Engineering ToolBox > Moist Air Properties

Psychrometric Table of Moist Humid Air Properties

Properties as

are indicated in the table below:

Temperature Saturation Pressure
(N/m2)
Humidity ratio at Saturation
(kgH2O/kgdry air)
Specific Volume Specific Enthalpy Specific Entropy
(kJ/kg dry air)
oC oF Dry Air
(m3/kg)
 Saturated Mixture
(m3/kg)
Dry Air
(kJ/kg dry air)
Saturated Mixture
(kJ/kg dry air)
-40 -40 12.84 0.000079 0.660 0.660 -22.4 -22.2 -90.7
-30 -22 38 0.00023 0.688 0.688 -12.3 -11.7 -46.7
-25 -13 63.25 0.00039 0.702 0.703 -7.27 -6.3 -24.7
-20 -4 103.2 0.00064 0.716 0.717 -2.23 -0.67 -2.2
-15 5 165.2 0.0010 0.731 0.732 2.79 5.3 21.2
-10 14 259.2 0.0016 0.745 0.747 7.8 11.8 46.1
-5 23 401.5 0.0025 0.759 0.762 12.9 19 73.4
0 32 610.8 0.0038 0.773 0.778 17.9 27.4 101.1
5 41 871.9 0.0054 0.788 0.794 22.9 36.5 137.4
10 50 1227 0.0077 0.802 0.812 27.9 47.2 175.5
15 59 1704 0.011 0.816 0.830 33 60 220.2
20 68 2337 0.015 0.830 0.850 38 75.4 273.3
25 77 3167 0.020 0.844 0.872 43 94.4 337.4
30 86 4243 0.027 0.859 0.896 48.1 117.8 415.6
35 95 5623 0.037 0.873 0.924 53.1 147.3 512.2
40 104 7378 0.049 0.887 0.957 58.1 184.5 532.3
45 113 9585 0.065 0.901 0.995 63.2 232 783.1
50 122 12339 0.087 0.915 1.042 68.2 293 975.3
55 131 14745 0.12 0.929 1.1 73.3 372 1221
60 140 19925 0.15 0.944 1.175 78.3 478 1544
65 149 25014 0.21 0.958 1.272 83.3 621 1974
70 158 31167 0.28 0.972 1.404 88.4 720 2565
75 167 38554 0.38 0.986 1.592 93.4 1110 3413
80 176 47365 0.55 1 1.879 98.5 1557 4711
85 185 57809 0.84 1.015 2.363 103.5 2321 6893
90 194 70112   1.03 3.340 108.6 3876 11281