Engineering ToolBox > Natural Gas - Pipe Sizing

Sizing low pressure natural gas pipe lines - imperial units

The tables below can be used for natural gas pipe sizing.

Steel Pipe - Schedule 40

Capacity of Pipe (MBH, ≈ CFH)
Pipe Size (in) Pipe Length (ft)
Nominal Inside diameter (I.D) 10 20 40 80 150 300
1/2 0.622 120 85 60 42 31 22
3/4 0.824 272 192 136 96 70 50
1 1.049 547 387 273 193 141 100
1 1/4 1.380 1200 849 600 424 310 219
1 1/2 1.610 1860 1316 930 658 480 340
2 2.067 3759 2658 1880 1330 971 686
2 1/2 2.469 6169 4362 3084 2189 1593 1126
3 3.068 11225 7938 5613 3969 2898 2049
4 4.026 23479 16602 11740 8301 6062 4287
5 5.047 42945 30367 21473 15183 11088 7841
6 6.065 69671 49265 34836 24632 17989 12720
8 7.981 141832 100290 70916 50145 36621 25895

natural gas pipe capacity diagram

For natural gas the nominal BTU/cf varies from about 900 to 1100 BTU/cf. In general it is common to set

Copper Tubing - type K

Capacity of Pipe (MBH, ≈ CFH)
Pipe Size (in) Pipe Length (ft)
Nominal Outside Diameter (O.D) Inside Diameter (I.D) 10 20 40 80
1/4 3/8 0.305 15 10 7 5
3/8 1/2 0.402 33 24 17 12
1/2 5/8 0.527 74 52 37 26
5/8 3/4 0.652 138 97 69 49
3/4 7/8 0.745 203 143 101 72
1 1 1/8 0.995 469 332 235 166
1 1/4 1 3/8 1.245 894 632 447 316

Copper Tubing - type L

Capacity of Pipe (MBH, ≈ CFH)
Pipe Size (in) Pipe Length (ft)
Nominal Outside Diameter (O.D) Inside Diameter (I.D) 10 20 40 80
1/4 3/8 0.315 16 11 8 6
3/8 1/2 0.430 41 29 20 14
1/2 5/8 0.545 81 58 41 29
5/8 3/4 0.666 146 103 73 52
3/4 7/8 0.785 236 167 118 84
1 1 1/8 1.025 511 362 256 181
1 1/4 1 3/8 1.265 936 662 468 331