Engineering ToolBox > NC - Noise Criterion

For a given noise spectrum, the NC rating can be obtained by plotting its octave band levels on the set of NC curves

Noise Criterion - NC - were established in U.S. for rating indoor noise, noise from air-conditioning equipment etc. In Europe it is common to use Noise Rating Curves - NR.

The method consists of a set of criteria curves extending from 63 to 8000 Hz, and a tangency rating procedure. The criteria curves define the limits of octave band spectra that must not be exceeded to meet occupant acceptance in certain spaces.

The NC rating can be obtained by plotting the octave band levels for a given noise spectrum - the NC curves. The noise spectrum is specified as having a NC rating same as the lowest NC curve which is not exceeded by the spectrum.

nc noise criteria diagram

Recommended Noise Criterion - NC

The noise in different types of rooms should not exceed the Noise Criterion limits listed below:

Type of Room - Space Type Recommended NC Level
NC Curve
Equivalent Sound Level
dBA
Apartments 25-35 35-45
Assembly Halls 25-30 35-40
Churches 30-35 40-45
Courtrooms 30-40 40-50
Factories 40-65 50-75
Hotels/Motels
- Individual rooms or suites 25-35 35-45
- Meeting or banquet rooms 25-35 35-45
- Service and Support Areas 40-45 45-50
- Halls, corridors, lobbies 35-40 50-55
Offices
- Conference rooms 25-30 35-40
- Private 30-35 40-45
- Open-plan areas 35-40 45-50
- Business machines/computers 40-45 50-55
Hospitals and Clinics
- Private rooms 25-30 35-40
- Operating rooms 25-30 35-40
- Wards 30-35 40-45
- Laboratories 35-40 45-50
- Corridors 30-35 40-45
- Public areas 35-40 45-50
Schools
- Lecture and classrooms 25-30 35-40
- Open-plan classrooms 35-40 45-50
Movie motion picture theaters 30-35 40-45
Libraries 35-40 40-50
Legitimate theaters 20-25 30-65
Private Residences 25-35 35-45
Restaurants 40-45 50-55
TV Broadcast studies 15-25 25-35
Recording Studios 15-20 25-30
Concert and recital halls 15-20 25-30
Sport Coliseums 45-55 55-65
Sound broadcasting 15-20 25-30

Example - Estimating NC - Noise Criterion

The Noise Criterion - NC - of a noise spectrum like

can be estimated to NC = 57 dB as indicated in the diagram below.

nc - noise criteria - example