The tables below can be used to indicate necessary capture velocity of evacuating air in a distance - x - from the outlet opening to avoid pollution products transferred to the surrounding room and environments.
The pollution source is in a distance - x - from the outlet opening.
| Process | Product speed | Velocity - v1 - | |
| m/s | fpm | ||
| Galvanic baths, stain baths, kitchen hoods, smith hoods etc. | small | 0.2 - 0.5 | 40 - 100 |
| Spray painting, unloading and loading of bags, welding etc. | moderate | 0.5 - 1.0 | 100 - 200 |
| Unloading moulds | high | 1.0 - 2.0 | 200 - 400 |
| Grinding, honing, sand blaster etc. | very high | 3.0 - 10.0 | 600 - 2000 |
| Process Baths | Required Capture Velocity - v1 - | |
| m/s | fpm | |
| Hardening | 0.4 | 80 |
| Stain, cold | 0.3 | 60 |
| Stain, hot | 0.5 | 100 |
| Defating | 0.3 | 60 |
| Galvanic, chrome or cadmium | 0.4 | 80 |
| Water, not boiling | 0.2 | 40 |
| Water, boiling | 0.4 | 80 |