Engineering ToolBox > Sound Attenuation in Duct Elbows

Attenuation in duct elbows is caused by reflected sound. It is only in big ducts and at high frequencies the attenuation is considerable.

Sound power level attenuation in elbows is based on sound reflection. Only in big ducts and at high frequencies is the attenuation considerable.

sound attenuation elbows

Attenuation in ducts at different sizes and at different frequencies for some common configurations can be taken from the table below.

Attenuation
(dB)
Width B
(mm)
Octave band center frequency Hz
125 250 500 1000 2000 4000 8000
Duct without insulation 125 0 0 0 6 8 4 3
250 0 0 6 8 4 3 3
500 0 6 8 4 3 3 3
1000 6 8 4 3 3 3 3
Insulation in front of elbow 125 0 0 0 6 8 6 8
250 0 0 6 8 6 8 11
500 0 6 8 6 8 11 11
1000 6 8 6 8 11 11 11
Insulation after the elbow 125 0 0 0 7 11 10 10
250 0 0 7 11 10 10 10
500 0 7 11 10 10 10 10
1000 7 11 10 10 10 10 10
Insulation in front and after the elbow 125 0 0 0 7 12 14 16
250 0 0 7 12 14 16 18
500 0 7 12 14 16 18 18
1000 7 12 14 16 18 18 18