Engineering ToolBox > US Design Outdoor Temperature and Relative Humidity - Winter and Summer
The table below can be used as an indication of design conditions in U.S cities summer and winter.
| State | City | January | July | ||||||
| Dry Bulb Temperature (oF) | Normal Relative Humidity (%) | Dry Bulb Temperature (oF) | Normal Relative Humidity (%) | ||||||
| 7:30 am. | 1:30 pm. | 7:30 pm. | 7:30 am. | 1:30 pm. | 7:30 pm. | ||||
| Alabama | Birmingham | 10 | 81 | 61 | 66 | 95 | 84 | 56 | 68 |
| Mobile | 10 | 95 | 90 | 64 | 78 | ||||
| Arizona | Flagstaff | -10 | 83 | 58 | 90 | 77 | 36 | ||
| Phoenix | 25 | 75 | 47 | 39 | 100 | 53 | 31 | 23 | |
| Yuma | 30 | 56 | 37 | 27 | 105 | 51 | 31 | 23 | |
| Arkansas | Little Rock | 5 | 80 | 67 | 68 | 110 | 85 | 55 | 59 |
| California | Eureka | 30 | 87 | 77 | 95 | 92 | 80 | ||
| Fresno | 25 | 93 | 80 | 66 | 90 | 61 | 36 | 20 | |
| Los Angeles | 35 | 63 | 46 | 51 | 105 | 85 | 50 | 54 | |
| Sacramento | 30 | 90 | 82 | 70 | 90 | 76 | 46 | 28 | |
| San Diego | 35 | 76 | 58 | 60 | 100 | 86 | 68 | 65 | |
| San Francisco | 35 | 84 | 69 | 70 | 85 | 92 | 75 | 78 | |
| Colorado | Denver | -10 | 54 | 37 | 41 | 85 | 55 | 27 | 30 |
| Grand Junction | -15 | 77 | 64 | 64 | 95 | 48 | 27 | 22 | |
| Pueblo | -20 | 67 | 44 | 48 | 95 | 73 | 34 | 35 | |
| Connecticut | New Haven | 0 | 75 | 65 | 69 | 95 | 77 | 64 | 74 |
| Delaware | Wilmington | 0 | 77 | 62 | 70 | 95 | 80 | 52 | 69 |
| District of Columbia | Washington | 0 | 73 | 56 | 64 | 95 | 78 | 52 | 64 |
| Florida | Jacksonville | 25 | 89 | 56 | 75 | 95 | 85 | 57 | 76 |
| Miami | 35 | 87 | 59 | 75 | 91 | 83 | 64 | 76 | |
| Georgia | Atlanta | 10 | 80 | 64 | 69 | 95 | 83 | 57 | 68 |
| Augusta | 10 | 84 | 59 | 69 | 98 | 83 | 55 | 69 | |
| Savannah | 20 | 83 | 58 | 72 | 95 | 85 | 61 | 80 | |
| Idaho | Boise | -10 | 82 | 75 | 74 | 95 | 54 | 34 | 23 |
| Lewiston | -5 | 79 | 73 | 71 | 95 | 64 | 37 | 25 | |
| Illinois | Cairo | 0 | 81 | 69 | 98 | 83 | 57 | ||
| Chicago | -10 | 81 | 70 | 75 | 95 | 78 | 51 | 55 | |
| Peoria | -10 | 73 | 72 | 77 | 96 | 81 | 53 | 58 | |
| Indiana | Fort Wayne | -10 | 84 | 75 | 81 | 95 | 84 | 53 | 58 |
| Indianapolis | -10 | 83 | 72 | 78 | 95 | 84 | 54 | 60 | |
| Terre Haute | 0 | 82 | 70 | 76 | 95 | 77 | 50 | 56 | |
| Iowa | Davenport | -15 | 95 | ||||||
| Sioux City | -20 | 78 | 67 | 72 | 95 | 86 | 55 | 54 | |
| Kansas | Dodge City | -10 | 78 | 57 | 61 | 95 | 77 | 45 | 52 |
| Topeka | -10 | 78 | 64 | 67 | 100 | 85 | 54 | 54 | |
| Kentucky | Louisville | 0 | 78 | 68 | 69 | 95 | 77 | 52 | 57 |
| Louisiana | New Orleans | 20 | 85 | 67 | 73 | 95 | 84 | 64 | 72 |
| Shreveport | 20 | 83 | 67 | 66 | 100 | 86 | 56 | 62 | |
| Maine | Portland | -5 | 81 | 65 | 74 | 90 | 78 | 58 | 76 |
| Maryland | Baltimore | 0 | 72 | 68 | 56 | 95 | 71 | 52 | 65 |
| Massachusetts | Boston | 0 | 72 | 59 | 67 | 92 | 72 | 55 | 70 |
| Michigan | Detroit | -10 | 82 | 71 | 77 | 95 | 74 | 50 | 56 |
| Grand Rapids | -10 | 85 | 78 | 80 | 95 | 76 | 51 | 54 | |
| Minnesota | Deluth | -25 | 78 | 74 | 74 | 93 | 87 | 61 | 66 |
| Minneapolis | -20 | 82 | 72 | 75 | 95 | 82 | 54 | 54 | |
| Mississippi | Vicksburg | 10 | 82 | 65 | 67 | 95 | 87 | 61 | 70 |
| Missouri | Kansas City | -10 | 78 | 64 | 66 | 100 | 76 | 48 | 47 |
| St. Louis | 0 | 77 | 65 | 68 | 95 | 73 | 50 | 55 | |
| Montana | Billings | -25 | 67 | 73 | 60 | 90 | 65 | 40 | 33 |
| Butte | -20 | 76 | 70 | 71 | 95 | 82 | 36 | 33 | |
| Nebraska | North Platte | -20 | 80 | 62 | 66 | 85 | 84 | 50 | 46 |
| Omaha | -10 | 82 | 68 | 73 | 65 | 780 | 51 | 51 | |
| Nevada | Reno | -5 | 82 | 67 | 54 | 95 | 72 | 25 | 20 |
| New Hampshire | Concord | -15 | 78 | 60 | 69 | 90 | 80 | 49 | 69 |
| New Jersey | Atlantic City | 5 | 79 | 68 | 74 | 95 | 81 | 72 | 82 |
| Newark | 0 | 72 | 79 | 65 | 95 | 75 | 51 | 65 | |
| Trenton | 0 | 73 | 62 | 68 | 95 | 77 | 55 | 68 | |
| New Mexico | Albuquerque | 0 | 68 | 51 | 46 | 95 | 59 | 33 | 28 |
| New York | Albany | -10 | 75 | 63 | 71 | 93 | 79 | 52 | 64 |
| Buffalo | -5 | 79 | 72 | 78 | 93 | 78 | 53 | 63 | |
| New York | 0 | 72 | 61 | 66 | 95 | 75 | 58 | 68 | |
| Rochester | -5 | 81 | 73 | 79 | 95 | 80 | 50 | 60 | |
| North Carolina | Asheville | 0 | 82 | 59 | 69 | 93 | 88 | 56 | 73 |
| Raleigh | 10 | 82 | 57 | 69 | 95 | 86 | 55 | 72 | |
| North Dakota | Bismarck | -30 | 77 | 71 | 75 | 95 | 85 | 52 | 49 |
| Ohio | Cincinnati | 0 | 82 | 70 | 74 | 95 | 84 | 52 | 60 |
| Cleveland | 0 | 81 | 72 | 79 | 95 | 79 | 52 | 58 | |
| Columbus | -10 | 83 | 71 | 76 | 95 | 78 | 52 | 60 | |
| Toledo | -10 | 79 | 72 | 75 | 95 | 76 | 52 | 59 | |
| Oklahoma | Oklahoma City | 0 | 79 | 62 | 65 | 101 | 80 | 49 | 51 |
| Oregon | Baker | -5 | 83 | 81 | 78 | 90 | 69 | 68 | 36 |
| Portland | 10 | 87 | 82 | 78 | 90 | 86 | 63 | 48 | |
| Pennsylvania | Harrisburg | 0 | 72 | 49 | 65 | 95 | 78 | 51 | 62 |
| Philadelphia | 0 | 74 | 65 | 68 | 95 | 78 | 52 | 65 | |
| Pittsburgh | 0 | 77 | 67 | 63 | 95 | 80 | 52 | 63 | |
| Scranton | -5 | 80 | 67 | 95 | 77 | 50 | |||
| Rhode Island | Providence | 0 | 73 | 60 | 67 | 93 | 79 | 57 | 73 |
| South Carolina | Charleston | 15 | 87 | 55 | 76 | 95 | 88 | 64 | 82 |
| Columbia | 10 | 81 | 57 | 65 | 95 | 83 | 56 | 68 | |
| South Dakota | Huron | -20 | 79 | 72 | 76 | 95 | 86 | 52 | 49 |
| Rapid City | -20 | 71 | 69 | 67 | 95 | 71 | 42 | 40 | |
| Tennessee | Knoxville | 0 | 83 | 65 | 69 | 95 | 83 | 55 | 66 |
| Memphis | 0 | 82 | 67 | 73 | 95 | 85 | 55 | 59 | |
| Texas | Amarillo | -10 | 71 | 51 | 52 | 100 | 77 | 43 | 42 |
| Corpus Christi | 20 | 88 | 66 | 75 | 95 | 93 | 58 | 68 | |
| Dallas | 10 | 81 | 62 | 62 | 100 | 79 | 50 | 47 | |
| El Paso | 10 | 63 | 45 | 39 | 100 | 60 | 37 | 30 | |
| Houston | 20 | 85 | 66 | 73 | 95 | 90 | 58 | 66 | |
| San Antonio | 20 | 82 | 60 | 59 | 100 | 88 | 49 | 45 | |
| Utah | Salt Lake City | -10 | 80 | 71 | 72 | 95 | 56 | 27 | 23 |
| Vermont | Burlington | -10 | 81 | 69 | 78 | 90 | 76 | 54 | 67 |
| Virginia | Richmond | 15 | 84 | 60 | 68 | 95 | 81 | 57 | 72 |
| Washington | Seattle | 15 | 86 | 80 | 74 | 85 | 86 | 63 | 47 |
| Walla Walla | -5 | 80 | 74 | 78 | 95 | 50 | 33 | 22 | |
| West Virginia | Charleston | 0 | 79 | 64 | 70 | 95 | 88 | 53 | 67 |
| Parkersburg | -10 | 82 | 66 | 74 | 95 | 80 | 52 | 65 | |
| Wisconsin | Green Bay | -15 | 75 | 68 | 73 | 95 | 85 | 58 | 64 |
| Milwaukee | -15 | 76 | 70 | 73 | 95 | 81 | 58 | 64 | |
| Wyoming | Cheyenne | -15 | 59 | 48 | 55 | 95 | 73 | 36 | 40 |