Engineering ToolBox > Rooms and Rates of Outdoor Make Up Air

Recommended rates of outdoor make up air in some common types of rooms - banks, assembly halls, hotels and many more

The rates of outdoor make up air in the table below can be used as a guideline in design of ventilation systems.


Type of Building and Room
Air Shifts
per hour
(1/h)
Airflow
(l/s per m2
floor area)
Outdoor
Airflow
(l/s)
Animals Sheep 3 per animal
Horses 40 per animal
Hens 3 per animal
Cows 100 per animal
Chickens 2 per animal
Pigs, sow 60 per animal
Piglet 15 per animal
Apartments 15 - 20 per person
Assembly halls 5 - 10 14 per person
Auditoriums 10 - 15 per person
Bakeries Production 8
Pastry room 6
Banks Service 2 - 3
Archive 1
Staff 2 - 3
Baths 5 - 8 15
Barber Shops 15 - 25 per person
Bars 15 - 25 per person
Beauty Shops 15 - 25 per person
Boiler rooms 4
Bowling Alleys 15 - 20 per person
Cafeterias 4 10 - 15 per person
Cinemas/Theatres 5 - 10 7 - 15 per person
Chemist's shops Sterile room 15
Laboratory 15
Packing room 4
Store 1
Churches 2 10 - 15 per person
Clubhouses 15 - 25 per person
Cocktail Lounges 15 - 25 per person
Computer Rooms 15 - 20 per person
Court Houses 10 - 15 per person
Dance halls 15 - 30 per person
Dental Clinics, Offices 15 - 20 per person
Department Stores (cfm/Sq.Ft) 0.3
Dining Halls 10 - 15 per person
Drug Shop 10 - 15 per person
Engine rooms 4
Exhibition halls 10 - 20
Fire Stations 15 - 20 per person
Garages 5 - 6 > 1
Hospitals General 25 per person
Therapy 9
Operating theatre 14
Autopsy 9
Hotels Reception 15 - 20 per person
Room 3
Industries Factory 20 - 30 per person
Carpenter work shop 2 - 5
Car repair shop 4
Car repair shop, exhaust outlet 60 - 80 per car
Mechanical work shop 3 - 4
Welding 12 - 15
Assembly 4 - 5
Jails 10 - 15 per person
Jewelry Shop 10 - 15 per person
Libraries 10 - 15 per person
Lunch Rooms, Luncheonettes 10 - 15 per person
Municipal Buildings 10 - 15 per person
Museums 10 - 15 per person
Smithies

6 - 7

Kitchens Small 20 - 40
Large 10 - 20
< 7 m2 15
> 7 m2 20
Industrial in general 25 - 30
Gas ovens 550/m2 outside wall
Electric ovens 300/m2 outside wall
Grill table 400/m2 outside wall
Frying pan 300
Boiling pan 100 l 100
Boiling pan 200 l 200
Coffee machine 60
Refrigerated cabinet 7 - 10
Cooling and freezer room 0.3 - 0.5
Store 2 - 4
Laundries 10 - 15
Lavatories 5 - 10 10
Night Clubs 15 - 25 per person
Malls 10 - 15 per person
Motels 15 - 20 per person
Offices Module 3 - 8 15 - 20 per person
Landscape 20 per person
Conference room 15 - 30 per person
Lecture room 10 - 15 per person
Dining hall 15 - 20 per person
Staff, changing clothes 8 - 12
Dining room 8 - 10
Resting room 15 per person
Police Stations 15 - 20 per person
Post Offices 15 - 20 per person
Precision Manufacturing 15 - 20 per person
Restaurants 5 - 10 10 15 - 20 per person
Retail Stores (cfm/Sq.Ft) 0.3
Schools Classroom 4 - 5 10 - 15 per person
Shops 20 per person
Shopping Centers 10 - 15 per person
Sports halls 3 - 4
Supermarkets 10 - 15 per person
Swimming pools 5 - 10
Taverns 15 - 25 per person
Town Halls 15 - 20 per person