Resources, Tools and Basic Information for Engineering and Design of Technical Applications!
mobile - visible on handheld devices - alternatively go to www.engineeringtoolbox.com!
Engineering ToolBox > Liquid Water Properties
Density, specific heat capacity, viscosity and thermal conductivity of liquid water at 1 atm or 14.7 psia, 1,000 psia and 10,000 psia are indicated below.
| Temperature (oF) | Density (lbm/ft3) | Specific Heat Capacity (Btu/lbm degR) | Viscosity (lbf sec/ft2) 10-7 |
| 32 | 62.42 | 1.007 | 366 |
| 40 | 62.42 | 1.004 | 323 |
| 50 | 62.42 | 1.002 | 272 |
| 60 | 62.38 | 1.000 | 235 |
| 70 | 62.31 | 0.999 | 204 |
| 80 | 62.23 | 0.998 | 177 |
| 90 | 62.11 | 0.998 | 160 |
| 100 | 62.00 | 0.998 | 142 |
| 110 | 61.88 | 0.999 | 126 |
| 120 | 61.73 | 0.999 | 114 |
| 130 | 61.54 | 0.999 | 105 |
| 140 | 61.39 | 0.999 | 96 |
| 150 | 61.20 | 1.000 | 89 |
| 160 | 61.01 | 1.001 | 83 |
| 170 | 60.79 | 1.002 | 77 |
| 180 | 60.57 | 1.003 | 72 |
| 190 | 60.35 | 1.004 | 68 |
| 200 | 60.10 | 1.005 | 62.5 |
| 212 | boiling point | ||
| Temperature (oF) | Density (lbm/ft3) | Specific Heat Capacity (Btu/lbm degR) | Viscosity (lbf sec/ft2) 10-7 |
| 32 | 62.62 | 0.999 | 365 |
| 40 | 62.62 | 0.997 | 323 |
| 50 | 62.62 | 0.995 | 272 |
| 60 | 62.58 | 0.994 | 235 |
| 70 | 62.50 | 0.994 | 204 |
| 80 | 62.42 | 0.994 | 177 |
| 90 | 62.31 | 0.994 | 160 |
| 100 | 62.19 | 0.994 | 142 |
| 110 | 61.03 | 0.994 | 126 |
| 120 | 61.88 | 0.995 | 114 |
| 130 | 61.73 | 0.995 | 105 |
| 140 | 61.58 | 0.996 | 96 |
| 150 | 61.39 | 0.996 | 89 |
| 160 | 61.20 | 0.997 | 83 |
| 170 | 60.98 | 0.998 | 77 |
| 180 | 60.75 | 0.999 | 72 |
| 190 | 60.53 | 1.001 | 68 |
| 200 | 60.31 | 1.002 | 63 |
| 250 | 59.03 | 1.001 | 48 |
| 300 | 57.54 | 1.024 | 38 |
| 350 | 55.83 | 1.044 | 32 |
| 400 | 53.91 | 1.072 | 28 |
| 500 | 49.11 | 1.181 | 22 |
| 544.58 | boiling point | ||
| Temperature (oF) | Density (lbm/ft3) | Specific Heat Capacity (Btu/lbm degR) | Viscosity (lbf sec/ft2) 10-7 |
| 32 | 64.5 | 0.937 | 357 |
| 40 | 64.5 | 0.945 | 315 |
| 50 | 64.5 | 0.951 | 267 |
| 60 | 64.1 | 0.956 | 233 |
| 70 | 64.1 | 0.960 | 204 |
| 80 | 64.1 | 0.962 | 176 |
| 90 | 63.7 | 0.964 | 159 |
| 100 | 63.7 | 0.965 | 142 |
| 110 | 63.7 | 0.966 | 126 |
| 120 | 63.3 | 0.967 | 114 |
| 130 | 63.3 | 0.968 | 105 |
| 140 | 63.3 | 0.969 | 98 |
| 150 | 63.0 | 0.970 | 91 |
| 160 | 62.9 | 0.971 | 85 |
| 170 | 62.5 | 0.972 | 79 |
| 180 | 62.5 | 0.973 | 74 |
| 190 | 62.1 | 0.974 | 70 |
| 200 | 62.1 | 0.975 | 65 |
| 250 | 60.6 | 0.981 | 51 |
| 300 | 59.5 | 0.988 | 41 |
| 350 | 58.1 | 0.999 | 35 |
| 400 | 56.5 | 1.011 | 31 |
| 500 | 52.9 | 1.051 | 25 |
| 600 | 48.3 | 1.118 | 21 |