Resources, Tools and Basic Information for Engineering and Design of Technical Applications!
mobile - visible on handheld devices - alternatively go to www.engineeringtoolbox.com!
Engineering ToolBox > Water Vapor - Weight in Air
Grains of moisture per pound of dry air at standard atmospheric pressure at relative humidity ranging 10 to 90%.
| Water Vapor in Air (grains water vapor/lb dry air) | ||||||||
| Relative Humidity (%) | Temperature (oC/oF) | |||||||
| -1 | 4 | 10 | 18 | 22 | 27 | 32 | 38 | |
| 30 | 40 | 50 | 60 | 70 | 80 | 90 | 100 | |
| 10 | 3 | 4 | 6 | 8 | 11 | 16 | 21 | 29 |
| 20 | 5 | 7 | 10 | 16 | 21 | 30 | 42 | 58 |
| 30 | 7 | 10 | 14 | 22 | 34 | 46 | 65 | 87 |
| 40 | 9 | 14 | 20 | 30 | 44 | 62 | 85 | 116 |
| 50 | 12 | 16 | 26 | 39 | 55 | 78 | 108 | 147 |
| 60 | 14 | 18 | 32 | 48 | 66 | 92 | 128 | 176 |
| 70 | 17 | 20 | 38 | 54 | 78 | 108 | 158 | 208 |
| 80 | 19 | 22 | 42 | 62 | 88 | 125 | 173 | |
| 90 | 21 | 24 | 48 | 70 | 100 | 140 | 195 | |